CC
CableCalcBS7671 · NFC · IEC
BS7671:2018+A2 · Section 525

Voltage Drop Calculator

Check cable voltage drop against the BS7671 Section 525 limits — 3% for lighting, 5% for other circuits — for any length, load and cable size.

BS7671:2018+A2
Size the cable
Design current Ib (A)
Device rating In (A)
Cable length (m)
Supply
Installation method
Insulation
Ambient temp (°C)
Circuits in group

Preset for a 20A single-phase circuit over 45m. The voltage drop result below updates as you change length, current or cable size. This tool checks the 5% non-lighting limit — for a 3%-limited lighting circuit, use the full calculator.

Minimum compliant size
4 mm²
Copper · PVC · multicore · method C
Compliant
Tabulated It36.0 A
Derated Iz36.0 A
Voltage drop9.90 V (4.30%)
Vd limit (5%)11.50 V
Ca ambient1.00
Cg grouping1.00
Ci insulation1.00
Combined factor1.000

Iz = It × Ca × Cg × Ci × Cc. Voltage drop uses the mV/A/m figures from BS7671 Appendix 4 and is checked against the 5% limit in Section 525 for non-lighting circuits. Adiabatic and fault-level checks need a prospective fault current — use the full calculator for those.

Full calculator — fault current, PDF export

How voltage drop is checked

Every conductor has resistance, so current flowing through it produces a voltage drop along its length. If that drop is too large, equipment at the far end receives a lower voltage than intended — motors run hot, lighting dims, and some equipment simply won't start reliably. BS7671 Section 525 limits this to 3% of nominal voltage for lighting circuits and 5% for other circuits, when supplied directly from a public low-voltage network.

The calculation

BS7671 Appendix 4 publishes a millivolt-drop-per-amp-per-metre (mV/A/m) figure for every cable size, insulation type and configuration. Voltage drop in volts is:

V = (Length × Ib × mV/A/m) / 1000

divided by the number of parallel cable sets if more than one is run per phase. That figure is then expressed as a percentage of the nominal voltage and compared against the 3% or 5% limit.

Why longer runs need larger cable even when current rating is satisfied

Voltage drop scales with length, but current-carrying capacity doesn't. A cable sized purely on current rating for a 5m run can be badly undersized for the same load at 40m — the load hasn't changed, but the accumulated resistive drop has. This is the single most common reason a cable that "should" work on paper fails a full BS7671 check, and it's why sub-main and outbuilding circuits — garages, EV chargers, garden rooms — are so often limited by voltage drop rather than by how much current the cable can physically carry.

Worked example

The preset loaded in the calculator above — a 20A single-phase circuit, PVC twin-and-earth, method C, 45m from the consumer unit — returns a minimum compliant size of 4mm², at 4.30% voltage drop against the 5% limit (11.5V of 230V). 2.5mm² already carries 20A comfortably on current rating alone (its tabulated rating under method C is 27A), so it's the voltage drop over the 45m run that pushes the result up to 4mm². This is a non-lighting circuit at the 5% limit — a lighting circuit at the tighter 3% limit would need an even larger cable over the same run. Enter your own circuit above to see the exact figures.

Questions

Frequently asked