BS7671:2018+A2 · Appendix 4

BS7671 Cable Current Rating Tables

Tabulated current-carrying capacities for PVC and XLPE copper cables, plus the ambient temperature and grouping correction factors, straight from BS7671:2018 Amendment 2 Appendix 4.

Every cable size shown by this calculator traces back to one of these tables. The tabulated rating It is the maximum current a cable can carry continuously at a 30°C ambient, installed alone, with no thermal insulation contact. Real installations rarely match those exact conditions, so It gets corrected down (or occasionally up) before it can be compared against a protective device rating — see the correction factors section below.

Table 4D1A — Multicore PVC, 70°C, copper

2 or 3 loaded conductors, e.g. twin-and-earth, PVC/PVC multicore, PVC/SWA/PVC — current-carrying capacity in amps
CSA mm²A1A2B1B2C
11110.51312.515
1.514.513.516.515.519.5
2.519.518.5232127
42625302836
63432383546
104643524863
166157696485
2580759084110
359992111103133
50119110133124159
70151139168156200
95182167201188241
120210192232216278
150240219258245318
185273248294278362
240321291344325424
300367334394371486

Table 4D2A — Single-core PVC, 70°C, copper

In free air, reference methods E and F — current-carrying capacity in amps
CSA mm²EF
11515
1.519.519.5
2.52727
43636
64646
106363
168585
25110114
35133141
50159170
70200213
95241256
120278293
150318336
185362383
240424449
300486515
400561600

Table 4E1A — Multicore XLPE, 90°C, copper

2 or 3 loaded conductors, e.g. XLPE/SWA/PVC, XLPE/LSZH — current-carrying capacity in amps
CSA mm²A1A2B1B2C
11312.51514.517.5
1.5171619.518.523
2.52322272531
43130363442
64038464354
105451635973
167368857998
259589112104129
35117110138129158
50141132168154191
70179167213194246
95216202258233298
120249233299268346
150285265344300395
185324300392341450
240380351461400530
300435402530460610

Table 4E2A — Single-core XLPE, 90°C, copper

In free air, reference methods E and F — current-carrying capacity in amps
CSA mm²EF
117.517.5
1.52323
2.53131
44242
65454
107373
169898
25129134
35158167
50191201
70246261
95298315
120346364
150395416
185450473
240530558
300610642
400718754

Correction factors

Apply the relevant factors to the tabulated rating: Iz = It × Ca × Cg × Ci × Cc. A cable is compliant when Iz is at least equal to the protective device rating In, and In is at least equal to the design current Ib.

Table 4B1 — Ambient temperature factor Ca

Correction applied when ambient temperature differs from the 30°C the tables assume
Ambient °CPVC (70°C)XLPE (90°C)
101.221.15
151.171.12
201.121.08
251.061.04
3011
350.940.96
400.870.91
450.790.87
500.710.82
550.610.76
600.50.71
650.350.65
700.58
750.5
800.41
850.29

Table 4C1 — Grouping factor Cg

Correction applied when multiple circuits are grouped together (bunched, in a duct, or on a tray)
Circuits in groupCg
11.00
20.80
30.70
40.65
50.60
60.57
70.54
80.52
90.50
100.48
120.45
140.43
160.41
200.38

Two further factors apply but aren't published as simple lookup tables here: Ci (thermal insulation contact — 1.00 with none, 0.75 touching on one side, 0.50 fully surrounded, per Regulation 523.9 / Table 52.2) and Cc (protective device — 1.00 for MCBs, MCCBs and RCDs, 0.725 for BS3036 semi-enclosed fuses).